38/66kV High Voltage Cable: Specifications, Standards, and Selection Guide

18, Nov. 2026

 

38/66kV High Voltage Cable: Specifications, Standards, and Selection Guide

A 38/66kV high voltage cable is designed for power networks with a nominal voltage of 66 kV between conductors and 38 kV between a conductor and earth. Buyers should confirm the required voltage designation, applicable standard, installation conditions, and accessory compatibility before requesting a quotation. Cable size and construction cannot be selected from voltage alone: current rating, route conditions, short-circuit duty, and project requirements also matter. This guide explains the specifications to review and the information to provide when comparing suppliers.

If you are looking for more details, kindly visit our website.

Who This Guide Is For

This guide is intended for utility engineers, EPC contractors, distributors, and industrial project buyers evaluating 38/66kV cable for a new installation or network upgrade. It is also useful for procurement teams preparing a technical inquiry or checking whether supplier offers are comparable. Because project specifications and national requirements vary, treat this information as a selection framework rather than a substitute for the approved cable design. Final requirements should be verified by the project’s responsible electrical engineer.

Understanding 38/66kV Cable Designations

In common IEC voltage notation, U0 is the rated power-frequency voltage between conductor and earth, U is the rated voltage between conductors, and Um is the highest voltage for which the equipment is designed. For a 38/66kV cable, the first two values are 38 kV and 66 kV respectively. The associated system voltage class is commonly expressed with a maximum system voltage of 72.5 kV, but buyers should confirm the exact designation required by the project specification and governing standard.

The voltage class describes insulation coordination, not the cable’s current-carrying capacity. Ampacity depends on conductor material and cross-section, installation method, ambient and soil conditions, grouping, and thermal properties of the surrounding environment. A cable selected for the correct voltage can still be unsuitable if its thermal or fault-duty requirements are not met.

Types, Materials, and Key Specifications

Typical Cable Construction

A common 38/66kV design uses a stranded copper or aluminum conductor, conductor screen, XLPE insulation, insulation screen, metallic screen, and outer sheath. The metallic screen provides an electrical return path and supports earthing arrangements defined by the system design. Depending on the route and installation environment, the construction may also include longitudinal or radial water-blocking measures, armor, or special sheath materials.

XLPE is widely used as insulation for high voltage extruded cables. A 90°C maximum continuous conductor temperature is commonly specified for XLPE cable designs, but the applicable limit must be confirmed against the cable standard, installation conditions, and project requirements. Do not assume that this temperature by itself determines the permissible operating current.

Specifications to Confirm

Specification What to define Why it matters
Voltage designation U0/U and required Um Confirms insulation class and system compatibility.
Conductor Copper or aluminum, cross-section, stranding, and conductor standard Affects resistance, weight, termination, and current rating.
Insulation and screens Insulation material, thickness, and screen construction Defines electrical design and interface requirements.
Metallic screen Material, cross-section, and bonding arrangement Must suit earth-fault duty and the network earthing design.
Sheath and protection Sheath material, water blocking, armor, and fire requirements Matches the cable to route conditions and environmental exposure.
Performance requirements Current rating, short-circuit duty, and specified tests Enables assessment against actual project operating conditions.

Standards and Compliance

IEC 60840 is an important standard to check for extruded-insulation power cables and accessories in voltage ranges above 30 kV up to the standard’s stated upper range. Confirm that the edition, cable voltage designation, and accessory scope match the project documents. IEC 60228 is commonly referenced for conductor requirements, while IEC 60287 provides methods for calculating cable current ratings under defined conditions.

Do not assume that a cable specified to IEC 60502-2 is automatically suitable for 38/66kV service. That standard addresses extruded-insulation cables in lower voltage ranges, so it should not be treated as the governing specification for this voltage class. Projects may also require national standards, utility specifications, or additional requirements for installation, accessories, or testing. Ask the buyer’s engineering team to identify the controlling documents and required revisions.

Matching Cable to the Application

For buried routes, review soil thermal resistivity, burial depth, duct arrangements, water exposure, and the possibility of multiple circuits in close proximity. These factors can change the allowable current rating, so provide route information when requesting ampacity calculations. For ducts or tunnels, consider ventilation, grouping, fire performance, and access for installation and maintenance.

For substations and industrial plants, the cable must also suit termination locations, bending constraints, earthing practices, and equipment interfaces. Metallic screen bonding—such as single-point, both-end, or cross-bonding arrangements—should be selected by the system designer because it affects induced sheath voltage and losses. Confirm cable and accessory interfaces together rather than treating the cable as an isolated purchase.

If you are looking for more details, kindly visit Zhongdong Cable Co., Ltd..

A Practical Selection Framework

  1. Confirm the electrical system. Provide nominal system voltage, maximum system voltage, earthing method, and operating frequency. State the required U0/U designation explicitly instead of relying on a shorthand voltage description.

  2. Define load and fault conditions. Share the design current, load profile where relevant, and short-circuit current and clearing time. Ask for the assumptions behind any proposed conductor size or current rating.

  3. Describe the route. Identify whether the cable will be buried directly, installed in ducts, laid in a tunnel, or routed above ground. Include route length, installation conditions, ambient information, grouping, and any moisture, chemical, or mechanical exposure.

  4. Set construction and compliance requirements. Specify conductor material, screen requirements, sheath type, water-blocking needs, armor if applicable, governing standards, and required inspections or tests. Identify any project-specific documents that take precedence over a general product standard.

  5. Check the complete system. Confirm that joints and terminations are suitable for the cable design, conductor size, voltage class, and installation environment. Review bonding, earthing, installation tools, and any required technical documentation before placing an order.

Pricing, MOQ, and Lead Time

The price of a 38/66kV cable depends on its design and order conditions rather than voltage designation alone. Conductor material and cross-section, metallic screen specification, sheath and protection options, testing scope, order quantity, and delivery destination can all affect a quotation. A meaningful comparison should use the same technical schedule and delivery basis for every supplier.

Minimum order quantity and lead time can vary with the required construction, production planning, material availability, and inspection requirements. We recommend asking suppliers to state the offered construction, quoted quantity basis, production schedule, and any assumptions or exclusions in writing. This helps procurement teams distinguish a like-for-like offer from one that omits technical or service requirements.

Supplier Evaluation Checklist

  • Can the supplier provide a clear data sheet showing the offered cable construction and voltage designation?
  • Does the offer identify the applicable standard and edition, along with any deviations from the inquiry?
  • Are conductor, screen, insulation, and sheath details stated rather than left as assumptions?
  • Can the supplier explain the basis of the proposed ampacity and short-circuit capability?
  • Are the required routine, sample, type, or project-specific tests identified in the quotation?
  • Can the supplier review accessory compatibility, packing, documentation, and delivery requirements?

At Zhongdong Cable Co., Ltd., we support B2B buyers reviewing high voltage cable requirements and preparing project-specific inquiries. To help us assess a 38/66kV request, share the voltage designation, applicable standard, conductor preference and size, installation route, required quantity, destination, and any testing or accessory requirements. We can then review the stated scope and clarify the information needed for a comparable proposal.

Conclusion: Make the Specification Project-Specific

Selecting a 38/66kV cable starts with confirming the voltage designation and governing standard, then matching the conductor and cable construction to the electrical duty and installation route. The most reliable purchasing decision also checks ampacity assumptions, short-circuit requirements, screen bonding, accessories, and project testing before comparing price or lead time. There is no single conductor size or sheath design that is suitable for every 66 kV network.

As a next step, prepare a technical inquiry with the system data, route conditions, applicable documents, quantity, and delivery requirements. Ask each supplier to identify its offered construction and any deviations, and have the project engineer verify the final design. Zhongdong Cable Co., Ltd. welcomes inquiries from buyers seeking to evaluate supply options for 38/66kV high voltage cable.

If you want to learn more, please visit our website 38/66kV High Voltage Cable.